Selection table for fixed compensation of motors

Motor
power
in PS

 Capacitor power in kvar
(dependent upon speed/Minute)

300015001000750500
2,5111,522,5
5222,53,54
7,52,533,54,55,5
10344,55,56,5
154567,59
20567912
2567910,514,5
3078101217
40910131521
501112,5161825
601314,5182028
701516,5202231
801719222434
901921242637
1002123262840
1202527303246
1503133363855
1803739424462
2004042454767
2254446495172
2504850536576

Note:

  • Values are guide values only

  • The capacitor power should be approx 90% of the idle motor power

  • Over-compensation must be avoided to avoid overexcitation

Selection table for fixed compensation of transformerstransformers

Transformer nominal power
in kVA
Capacitor
nominal power
in kvar
1005
1606,25
2007,5
25010
31512,5
40015
50020
63025
80030
1 000 40
1 250 50
1 600 60
2 000 80

Note:

  • Values are guide values only

  • Regional regulations of energy supply companies must be observed

  • Pay attention to the respective back-up fuses and short-circuit proof cables