TypeWH6165DVH3113MDVH3106
Item number14.01.02014.01.02114.01.022
Accuracy class12 (1 optional)1
Protection class222
Direct measurement Basis / Limit10 / 65A5 / 65A-
Current transformer--../5A*1
Power consumption in current path--<1,0VA
Current inputs sep. galvanically--Yes
Minimum working current40mA25mA25mA
Measuring voltage230V+/-10%3x230/400V +-10%3x230/400V +-10%
Self consumption<1,5VA<1,5VA<1,5VA
Frequency50/60Hz50/60Hz50/60Hz
Pulse output SO value1000 pulses/kWh500 pulses/kWh5000 pulses/kWh
Pulse widthmin. 30msmin. 30msmin. 30ms
Loadup to 230V AC /100mA
Number of digits6,16,15,2
PTB accreditationYesYesYes
Calibratableoptionaloptionaloptional
Protection housing/terminals IP51/IP20

Connection diameter

up to 16qmmup to 25qmmcurrent:10qmm
voltage: 2,5qmm
Width36mm 2TE125mm 7TE125mm 7TE
DimensionsB36xH96xT66mmB125xH96xT66mmB125xH96xT66mm
Weight140g500g500g
Operating temperature-20 .. +55°C-20 .. +55°C-20 .. +55°C
Storage temperature-25 .. +70°C-25 .. +70°C-25 .. +70°C