Compact design KB4, KB6, KB8, KB10

KB4: H=600, B=400, T=250, A1=23, A2=421, A3=560
KB8: H=800, B=600, T=250, A1=23, A2=620, A3=756

This is a space-saving design for smaller nominal power levels and wall mounting.

Technical data:

  • Norminal voltage: 400 V, 3-phase, 50 Hz
  • Protection class: IP32
  • Cooling: Natural – pay attention to sufficient convection
  • Controller: Prophi with AUTO configuration
  • Reactor: No reactor
Compact design KB4, KB6, KB8, KB10
Nominal power
kvar
Level power
kvar
Switching
ratio
TypeItem numberkgVersion
7,52,5/51:2JF440/7,5ER3KB4**50.39.00525KB4
102,5/2,5/51:1:2JF440/10ER4KB4**50.39.01525KB4
12,52,5/5/51:2:2JF440/12,5ER5KB4**50.39.03025KB4
155/101:2JF440/15ER3KB4**50.39.04526KB4
17,52,5/5/101:2:4JF440/17,5/ER7KB4**50.39.06026KB4
205/5/101:1:2JF440/20ER4KB4**50.39.07529KB4
255/10/101:2:2JF440/25ER5KB4**50.39.09527KB4
27,52,5/5/101:2:4:4JF440/27,5ER11KB4**50.39.12027KB4
316,2/12,51:2:2JF440/31ER5KB4**50.39.14535KB4
355/10/201:2:4JF440/35ER7KB4**50.39.17535KB4
4010/10/201:1:2JF440/40ER4KB4**50.39.19536KB4
455/10/15..1:2:3:3JF440/45ER9KB4**50.39.22037KB4
5010/20/201:2:2JF440/50ER5KB4**50.39.23538KB4
555/10/201:2:4:4JF440/55ER11KB8**50.39.27077KB8
6010/20/301:2:3JF440/60ER6KB8**50.39.29578KB8
7010/20/401:2:4JF440/70ER7KB8**50.39.32078KB8
7512/12/251:1:2:2JF440/75ER6KB8**50.39.34570KB8
8020/20/401:1:2JF440/80ER4KB8**50.39.37092KB8
9010/20/301:2:3:3JF440/90ER9KB8**50.39.39594KB8
10012/12/251:1:2:4JF440/100ER8KB8**50.39.42095KB8
10020/40/401:2:2JF440/100ER5KB8**50.39.43095KB8
11010/20/401:2:4:4JF440/110ER11KB8**50.39.44096KB8
12020/20/401:1:2:2JF440/120ER6KB8**50.39.45097KB8

Other nominal voltages, frequencies, powers, mechanical designs or versions with circuit breaker are available upon request.

Dynamic PFC in extractable module design

ES8184: H=1835, B=800, T=400, A1=374,
A2=25, A3=700, A4=100, A5=1480

Application: automatically regulated PFC modules in extractable module design, built into steel cabinets constructed in extractable module design in which the output can be expanded as required.

Technical data:

  • Norminal voltage: 400 V, 3-phase, 50 Hz
  • Protection class: IP32
  • Cooling: Natural – pay attention to sufficient convection
  • Controller: Prophi with AUTO configuration
  • Reactor: No reactor
Modular design ES8184
Nominal power
kvar
Step power
kvar
Switching
ratio
TypeItem numberkgWidth
15025/25/501:1:2...JF440/150ER6ES8184**50.81.400208
15012/12/251:1:2:4..JF440/150ER12ES8184**50.81.415208
15025/25/251:1:1...JF440/150ER6ES8184**50.81.425208
16020/20/401:1:2...JF440/160ER8ES8184**50.81.450209
17525/50/501:2:2...JF440/175ER7ES8184**50.81.475210
17512/12/251:1:2...JF440/175ER14ES8184***50.81.490210
18020/40/401:2:2...JF440/180ER9ES8184**50.81.515211
20050/501:1...JF440/200ER4ES8184**50.81.540212
20025/25/501:1:2:...JF440/200ER8ES8184**50.81.550212
20012/12/251:1:2:4...JF440/200/ER16ES8184**50.81.560212
20020/20/401:1:2...JF440/200ER10ES8184**50.81.570212
24020/20/401:1:2...JF440/240ER12ES8184***50.81.600232
250501:1:1...JF440/250ER5ES8184**50.81.625232
25025/25/501:1:2...JF440/250ER10ES8184**50.81.635232
25012/12/251:1.2:4...JF440/250ER20ES8184***50.81.645232
30050/501:1:1...JF440/300ER6ES8184**50.81.670236
30025/25/501:1:2...JF440/300ER12ES8184***50.81.680236
30012/12/251:1:2:4...JF440/300ER24ES8184***50.81.690236
400
500
600
AccessoriesTypeItem numberKg
Sockel 100mm hochSO 100/800/40029.03.3175
Sockel 200mm hochSO 200/800/40029.03.32210

** with power factor controller Prophi 6R
*** with power factor controller Prophi 12R

Extension units, units in ISO housing and audio frequency blocks are available upon request. Other nominal voltages, frequencies, powers, mechanical designs or versions with circuit breakers are available upon request.

Automatic PFC system on mounting plate (without reactors)

MP4: H=555, B=350, T=250, A1=323, A2=525
MP8: H=750, B=550, T=250, A1=525, A2=723

Applications: This is the compact design of a PFC system on mounting plate for installation in existing switchboard cabinets or distributionboards. For grids with low harmonic content.

Technical data:

  • Norminal voltage: 400 V, 3-phase, 50 Hz
  • Protection class: IP32
  • Cooling: Natural – pay attention to sufficient convection
  • Controller: Prophi with AUTO configuration
  • Reactor: No reactor
Mounting plate MP4, MP8
Nominal power
kvar
Level power
kvar
Switching
ratio
TypeItem numberKg
7,52,5/51:2JF440/7,5ER3MP4**50.33.00510
102,5/2,5/51:1:2JF440/10ER4MP4**50.33.01510
12,52,5/5/51:2:2JF440/12,5ER5MP4**50.33.03010
155/101:2JF440/15ER3MP4**50.33.04511
17,52,5/5/101:2:4JF440/17,5/ER7MP4**50.33.06011
205/5/101:1:2JF440/20ER4MP4**50.33.07514
255/10/101:2:2JF440/25ER5MP4**50.33.09514
27,52,5/5/101:2:4:4JF440/27,5ER11MP8**50.33.12029
316,2/12,51:2:2JF440/31ER5MP4**50.33.14526
355/10/201:2:4JF440/35ER7MP4**50.33.17526
4010/10/201:1:2JF440/40ER4MP4**50.33.19528
455/10/151:2:3:3JF440/45ER9MP4**50.33.22028
5010/20/201:2:2JF440/50ER5MP4**50.33.24529
555/10/201:2:4:4JF440/55ER11MP8**50.33.27029
6010/20/301:2:3JF440/60ER6MP8**50.33.29530
7010/20/401:2:4JF440/70ER7MP8**50.33.32031
7512/12/251:1:2:2JF440/75ER6MP8**50.33.34532
8020/20/401:1:2JF440/80ER4MP8**50.33.37035
9010/20/301:2:3JF440/90ER9MP8**50.33.39537
10012/12/251:1:2:4JF440/100ER8MP8**50.33.42038
10020/40/401:2:2JF440/100ER5MP8**50.33.43038
11010/20/401:2:4JF440/110ER11MP8**50.33.44039
12020/20/401:1:2:2JF440/120ER6MP8**50.33.45040

Other nominal voltages, frequencies, powers, mechanical designs or versions with circuit breaker are available upon request.

Power factor correction system on extractable module – M084 (without reactor)

MO84: H=330, B=703, T=333,
A1=290, A2=14, A3=26.5

Applications: This is a ready to install extractable module for PFC for installation in existing switchboard cabinets or low voltage distribution boards.

Technical data:

  • Norminal voltage: 400 V, 3-phase, 50 Hz
  • Protection class: IP32
  • Cooling: Natural – pay attention to sufficient convection
  • Controller: Prophi with AUTO configuration
  • Reactor: No reactor
PFC module MO84
Nominal power
kvar
Level power
kvar
Switching
ratio
TypeItem numberKg
5050 JF440/50EK1MO8450.80.70022
5025/251:1JF440/50/2EK2MO8450.80.74022
5010/20/201:2:2JF440/50/3EK5MO8450.80.77022
5012/12/251:1:2JF440/50/3/EK4MO8450.80.77422
6020/401:2JF440/60/2EK3MO8450.80.77523
6010/10/201:1:2JF440/60/4EK6MO8450.80.77623
7525/501:2JF440/75/2EK3MO8450.80.80024
7525/25/251:1JF440/75/3EK3MO8450.80.81024
7512/12/251:1:2:2JF440/75/4EK6MO8450.80.81124
8040/401:1JF440/80/2EK2MO8450.80.83524
8020/20/401:1:2JF440/80/3EK4MO8450.80.83724
10050/501:1JF440/100/2EK2MO8450.80.87525
10025/25/501:1:2JF440/100/3EK4MO8450.80.88025
10025/25/251:1:1JF440/100/4EK4MO8450.80.90025
10020/40/401:2:2JF440/100/3EK5MO8450.80.90225
10012/12/251:1:2:4JF440/100/4EK8MO8450.80.90325
Control module with 6R Prophi controller,
fuse separation switch,
current transformer clamp and 2m connection cable
(mounted on the capacitor module)
50.80.003 
Control module with 12R Prophi controller,
fuse separation switch,
current transformer clamp and 2m connection cable
(mounted on the capacitor module)
50.80.004 
Accessories
Fixing rail for Rittal cabinet on the  left
Fixing rail for Rittal cabinet on the right

29.12.435
29.12.436
 

** with Power factor controller Prophi 6R, audio frequency blocking circuits are available upon request.

Other nominal voltages, frequencies, powers, mechanical designs or versions with circuit breaker are available upon request.