| Standards | | IEC 60831-1+2, EN 60831-1+2 |
| Overvoltage | Umax | Un + 10% (up to 8 h each day) / Un + 15% (up to 30 min each day) |
| | Un + 20% (up to 5 min each day) / Un + 30% (up to 1 min each day) |
| Excess current | Imax | Up to 1.3 · In (up to 1,5 x In combined effects from harmonics) |
| | (overvoltage and capacity tolerance) |
| Inrush current | IS | Up to 300 x In |
| Losses | | Approx. 0.2 Watt per kvar |
| Nominal frequency | f | 50 / 60 Hz |
| Capacity tolerance | | – 5% / +10% |
| Test voltage(terminal/terminal) | VTT | 2.15 · Vn1, AC, 10 s |
| Test voltage(terminal/casing) | VTC | Up to Un≤ 660 V: 3 000 VAC, 10 s; over Un = 660 V: 6 000 VAC, 10 s |
| Average life expectancy | t LD(Co) | Up to 150 000 h |
| Environmental temperature | | –25/D; max. temp. 55 °C; max. 24 hour average = 45 °C; |
| | max. 1 year average = 35 °C; lowest temperature = –40 °C |
| Cooling | | Natural or forced air cooling |
| Air humidity | Hrel | max. 95% |
| Operation height | | max. 4000 m above sea level |
| Fixing and earth | | M12 thread bolts on the housing bottom |
| Safety | | Dry technology, over pressure tear-off fuse, selfhealing, maximum permitted |
| | fault current 10000A in accordance with UL810 standard |
| Discharge | | Discharge resistance |
| Housing | | Aluminium can and steel housing |
| Protection class | | IP20, indoor (optional with terminal cover, IP54) |
| Dielectric | | Polypropylene film |
| Coating | | Dry |
| Number of switching cycles per year | | Maximum 500 switch cycles in accordance with IEC6083 |