Multifunction power analyser with RCM

The multi-purpose unit for integration into control panels. Continuous monitoring of the power quality, analysis of electrical interference in the event of network problems.

 

Show device backShow device front
Overview of all basic data

Communication

  • Profibus (DP/V0)
  • Modbus (RTU, TCP, Gateway)
  • TCP/IP
  • BACnet (optional)
  • HTTP (Homepage)
  • FTP (File transfer)
  • SNMP
  • TFTP 
  • NTP (time synchronisation)
  • SMTP (email function)
  • DHCP

Interfaces

  • Ethernet
  • Profibus / RS485 (DSUB-9)
  • RS485 Modbus (terminal strip)

Accuracy of measurement

  • Energy: Class 0.2S (... / 5 A)
  • Strom: 0,2 %
  • Spannung: 0,1 %

Power quality

  • Harmonics up to 63th harmonic
  • Short-term interruptions (> 20 ms)
  • Transient recorder (> 50 μs)
  • Starting currents (> 20 ms)
  • Unbalance

Networks

  • IT, TN, TT networks
  • 3 and 4-phase networks
  • Up to 4 single-phase networks

Measured data memory

  • 256 MByte Flash
  • 32 MB SDRAM

PLC functionality

  • Graphical programming
  • Jasic® programming language
  • Programming of threshold values etc.

2 digital inputs

  • Pulse input
  • Logic input
  • State monitoring
  • HT / LT switching

2 digital outputs (UMG 96)

  • Pulse output kWh / kvarh
  • Switch output
  • Threshold value output
  • Logic output

Thermistor input

  • PT100, PT1000, KTY83, KTY84

RCM – Residual Current Monitoring

  • 2 residual current inputs

Network visualisation software

  • GridVis®-Basic (in the scope of supply)

Areas of application

  • Continuous monitoring of the power quality
  • Energy management systems (ISO 50001)
  • Master device with Ethernet gateway for subordinate measurement points
  • Visualisation of the energy supply in the LVDB
  • Analysis of electrical disturbances in the event of power quality problems
  • Cost centre analysis
  • Remote monitoring in the property operation
  • Use in test fields (e.g. in universities)

Article number

52.26.001, 52.26.003