Ports, protocols and connections

Ports, protocols and connections

UMG 604 / UMG 605 / UMG 508 / UMG 511

Protocols Ports
TFTP 1201
Modbus / TCP – Modbus / UDP 502, 4 Ports
DHCP 68
NTP 123
BACnet 47808
Nameservice 1200
HTTP 80
FTP 21
FTP data port 1024, 1025
FTP data port 1026, 1027
Modbus over Ethernet 8000, 1 Port
Service port (telnet) 1239
SNMP 161 / 162 (TRAP)
E-Mail port (actual) 25
E-Mail port (in preparation) 587

UMG 103 / UMG 104

Protocols Ports
The devices do not have an Ethernet connection The devices do not have an Ethernet connection

GridVis®

Protocols Ports
Modbus / TCP – Modbus / UDP 502
HTTP 80
FTP 21
FTP data port 1024, 1025
FTP data port 1026, 1027
Modbus / TCP 502
Modbus over Ethernet 8000
Read out telnet data port 1239
Update telnet data port 1236, 1237
E-Mail port (in preparation) 25
E-Mail port (in preparation) 587
Fig.: TCP group: max. 24 connections (queue scheduling) (UMG 604 / 605 / 508 / 511)
Fig.: TCP group: max. 24 connections (queue scheduling) (UMG 604 / 605 / 508 / 511)

Number of TCP/UTP connections (UMG 604 / 605 / 508 / 511)

  • A max. total of 24 connections are possible via the TCP group. The following applies:
    • Port 21 (FTP): max. 4 connections
    • Port 25/587 (E-Mail): max. 8 connections
    • Port 1024-1027 (data port to every FTP port): max. 4 connections - Port 80 (HTTP): max. 24 connections
    • Port 502 (ModbusTCP/IP): max. 4 connections
    • Port 1239 (Debug): max. 1 connection
    • Port 8000 (Modbus orTCP/IP): max. 1 connection

Fig.: UTP group: Connection-free communication (UMG 604 / 605 / 508 / 511)
Fig.: UTP group: Connection-free communication (UMG 604 / 605 / 508 / 511)
  • Connection-free communication via the UTP group
    • Port 68 (DHCP)
    • Port 123 (NTP)
    • Port 161/162 (SNMP)
    • Port 1200 (Nameservice) - Port 1201 (TFTP)
    • Port 47808 (BACnet)

The UMG 96RM-E supports the following protocols via Ethernet connection

Client services Ports
DNS 53 (UDP / TCP)
DHCP-Client (BootP) 68 (UDP)
NTP (Client) 123 (UDP)
E-Mail (sending) Selectable (1-65535 TCP)
Server services Ports
Ping ICMP / IP)
FTP 20 (TCP)*, 21 (TCP)
HTTP 80 (TCP)
NTP (only listen) 123 (UDP Broadcast)
SNMP 161 (UDP)
Modbus TCP 502 (UDP / TCP)
Geräte-Identifikation 1111 (UDP)
Telnet 1239 (TCP)
Modbus RTU (Ethernet encapsulated) 8000 (UDP)

* Random port (> 1023) for data transfer, if work is taking place in PASSIVE mode

The UMG 96RM-E can administrate 20TCP connections.

Client services are contacted by a device on a server via the specified ports, the server services make the device available.

The following protocols are not supported. BACnet (47808 / UDP)

Survey about Janitza

To optimize our services and offers we would like to ask you just one simple question.

It's completely anonymous and takes less than a minute to answer.

Let's go!

How did you learn
about our company?

Fields marked with an * are mandatory.

Thank you for your participation!

We'll be able to improve our services and offers upon your answers.

Close survey

Do you want to return to our survey later?

Yes, I'll answer it later