UMG 96-PA basic device

General

  • Accuracy of measurement with voltage, current 0.2% 
  • Accuracy of measurement with active energy (kWh, .../5 A) Class 0.2S 

Supply voltage

  • AC 90V – 277V (50/60) Hz or DC 90V – 250V, 300V CAT III

Inputs and outputs

  • 3 digital inputs and outputs
  • 1 analogue output

RMS - momentary values, e.g.:

  • Current, voltage, frequency
  • Effective, reactive and apparent power
  • Power factor

Energy measurement

  • Active, reactive and apparent energy
  • Tariffs: HT / LT

Environmental conditions

  • Temperature range, operation: K55 (–10 to +55 °C) 

Recording of the mean values, e.g.:

  • Voltage, current / live and maximum
  • Active, reactive and apparent power / present and maximum
  • Frequency / present and maximum

Measurement of the power quality

  • Harmonics per order / current and voltage: 1.–25. (with MID), 1.-40. (without MID)
  • Distortion factorTHD-U /THD-I in %
  • Current and voltage, positive, zero and negative sequence component

Measured data recording

  • 4 MB Memory (Flash)
  • Mean, minimum, maximum values

Interface / protocol

  • RS485 / Modbus RTU

Programming / threshold values / alarm management

  • Comparator (2 Groups with 3 comparators each)

Network visualisation software

  • GridVis®-Basic (in the scope of supply)

Optional additional functions with the packages GridVis®-Professional, GridVis®-Service and GridVis®-Ultimate available.

Measured voltage input (3 x)

  • Overvoltage category: 600 V CAT III 
  • Metering range, voltage L-N, AC (without transformer): 0 - 600 Vrms (± 10%) 
  • Metering range, voltage L-L, AC (without transformer): 0 - 1040 Vrms (± 10%) 
  • Frequency measuring range: 45 to 65 Hz 
  • Sampling rate per channel (50 / 60 Hz): 8.33 kHz 
  • Measurement in quadrants: 4
  • Networks: TN, TT 

Measured current input (3 x)

  • Rated current: 1 / 5A 
  • Overvoltage category: 300 V CAT II 
  • Sampling rate: 8.33 kHz 

Mechanical properties

  • Net weight (with attached connectors): approx. 250 g
  • Device dimensions in mm (H x W x D): 96 x 96 x 86 
  • Protection class per EN 60529 (with sealing = IP54): Front IP40 / back IP20 
  • Assembly per IEC EN 60999-1 / DIN EN 50022: Front panel installation 

Article number

UMG 96-PA basic device without MID
90-277 V AC / 90-250 V DC, CAT III

52.32.001

5232001

UMG 96-PA basic device without MID 
24-90 V AC / 24-90 V DC, CAT III

52.32.002

5232002

UMG 96-PA basic device with MID 
90-277 V AC / 90-250 V DC, CAT III

52.32.003

5232003

Modules for the UMG 96-PA

Residual current input

  • Analogue inputs: 2 for residual current or analogue measurement 
  • Rated current: 30 mA rms
  • Triggering current: 50 μA
  • Resolution: 1 μA 

Temperature measurement (1 x)

  • Update time: 1 second
  • Connectable sensors: PT100, PT1000, KTY83, KTY84 

Interface

  • Ethernet connection RJ45

Current measurement I4

  • Rated current: 1 / 5A
  • Overvoltage category: 300 V CAT II
  • Power consumption: Approx. 0.2 VA (Ri = 5 mOhm) 
  • Sampling rate: 8.33 kHz 

Article number

Module without
Ethernet connection (RJ45)

52.32.011

5232011

Module with
Ethernet connection (RJ45)

52.32.010

5232010