Technical details
Item no.: see product variants



Data at a glance
Product variants
Functions and features
Option DI: Pulse input for additional measurements
- Optional digital input for recording any process variables (e.g. compressed air or water)
- Measured values are standardized and temporarily stored in the AKM
Option RCM plus: Extended residual current measurement
- Detection of pulsating fault currents up to 20 kHz (type B+) according to IEC 62020
- Alternative to insulation measurement in TN-S systems and thus reduced testing effort on fixed electrical installations within the scope of DGUV V3
Option DI: Pulse input for additional measurements
- Optional digital input for recording any process variables (e.g. compressed air or water)
- Measured values are standardized and temporarily stored in the AKM
General features
- Measuring device UMG 96RM-E or UMG 806 (depending on type)
- Current measurement 3-phase and direct measurement of the neutral conductor current
- Fault current measurement type A with integrated differential current transformer CT-AC RCM 35N
- Measurement of box internal temperature with PT100 sensor
- Power output fused with NH fuses (max. current depending on type)
- Communication: 1x RJ45 (Ethernet), 2x M12 (Modbus)
- Type tested according to DIN EN 61439
- Freely selectable cable outlet direction simplifies installation
- Display can be rotated by 180° for laterally correct display
- Easy bus installation due to master-slave structures
- Cost and IP address saving networking via RS485